Filter Concepts Inc.

GROUND INDUCTOR FILTERS
GF SERIES

System EMI Filter with Ground Isolator

A system filter with good general purpose performance, the GF Series was designed for AC input and distribution applications.

GF filters include an alternate ground termination for the AC input power to isolate AC mains' high frequency low impedance ground noise.

 

Schematic

Schematic-GF SERIES

 

click on the to go the mechanical drawing

Part Number1
Current
Flange
Connector
End Mount
Leakage2

GF10
10.0A
--
--
1.0mA

GF20
20.0A
--
--
1.0mA

GF30
30.0A
--
--
1.5mA

Rated Voltage: 250VAC, 50/60Hz

Test Voltage: Line to Line: 1.7 KVDC
Line to Gnd: 2.2 KVDC

Insertion Loss: (50 ohms, typical)

.05MHz
.15MHz
.50MHz
1.5MHz
5.0MHz
20MHz
L/L
6db
20db
45db
55db
55db
50db
L/G3
10db
22db
32db
45db
50db
50db

1 See Filter Order Information for complete part number
2 Each line to ground @ 250VAC/5OHz
3 "B" option can add up to 6db in application

 