Filter Concepts Inc.

3C SERIES

3 Phase SCR Line Filter

SCR input line filter designed to suppress transients generated by thyristor phase regulation circuits, industrial controllers and power supplies. 

Schematics
Schematic-3C SERIES
Delta

Wye

 

click on the to go the mechanical drawing 

Part Number1
Current
Flange
End Mount
Leakage2

3C20D
20A/PH
1.6mA

3C20
20A/PH
1.6mA

3C40D
40A/PH
2.4mA

3C40
40A/PH
2.4mA

3C60D
60A/PH
2.4mA

3C60
60A/PH
2.4mA

3C100D
100A/PH
2.4mA

3C100
100A/PH
2.4mA

Rated Voltage: 250VAC, 50/60Hz

Test Voltage: Line to Line: 1.2 KVDC
Line to Gnd: 2.2 KVDC

Insertion Loss: (50 ohms, typical)

.05MHz
.15MHz
.50MHz
1.5MHz
5.0MHz
20MHz
L/L
50db
60db
65db
65db
65db
60db
L/G
5db
18db
40db
55db
60db
50db

1 See Filter Order Information for complete part number