Filter Concepts Inc.

3W SERIES

3 Phase Wide Band High Performance Filter

3W Series provides extended high and low frequency insertion loss while maintaining low ground leakage currents.

The unique design of the 3W filter maintains performance over a wide range of input and output impedances.

 

Schematic
Schematic-3W SERIES
Schematic-3W -Y SERIES
Delta

Wye

 

click on the to go the mechanical drawing 

Current

Current

Part Number1
50/60Hz
400Hz
Flange
End Mount
Leakage2

3W2
2.5A/PH
2.5A/PH
1.5mA
3W2D
2.5A/PH
2.5A/PH
1.5mA
3W5
5A/PH
5A/PH
3.6mA
3W5D
5A/PH
5A/PH
3.6mA
3W10
10A/PH
10A/PH
3.6mA

3W10D
10A/PH
10A/PH
3.6mA

3W20
20A/PH
18A/PH
3.6mA

3W20D
20A/PH
18A/PH
3.6mA

3W30
30A/PH
25A/PH
3.6mA

3W30D
30A/PH
25A/PH
3.6mA

3W45
45A/PH
40A/PH
3.6mA
3W45D
45A/PH
40A/PH
3.6mA

 

Rated Voltage 250/440 VAC @50/60 Hz
Rated Voltage 125/220 VAC @ 400 Hz

Test Voltage: Line to Line: 2.2 KVDC
Line to Gnd: 2.2 KVDC

Insertion Loss: (50 ohms, typical)

 

 
.05MHz
.15MHz
.50MHz
1.5MHz
5.0MHz
50MHz
L/N
 
52db
65db
65db
65db
65db
60db
L/G
 
40db
60db
65db
65db
65db
60db

1 See Filter Order Information for complete part number
2 Each line to ground @ 250VAC/5OHz

 

Main | Application Notes | Filter Finder | AC Filters | DC Filters
Three Phase Filters | Home Automation Filters | Custom EMI Filters

google-plus linkedin twitter facebook


EMI Filter division, 22895 East Park Drive, Yorba Linda, CA 92887, USA
Tel: (714)221-4056, Fax: (714)289-2149, Toll Free: +1-800-527-4362